PSM INSTRUMENTATION LTD coming soon....
High accuracy Radar gauging for marine & industrial applications
Intelligent Radar Transmitter
employing FMCW Technology
Benefits at a glance Non-contact radar measurement
4-20mA output
Choice of antenna types
Hart, Modbus, Profibus interface options
Accurate to 5mm on ranges up to 30 metres with 2mm repeatability
9.9GHz Quartz controlled all digital processing
PLL- stabilised FMCW X-band antenna.
PSM can now offer RADAR level gauges to provide the very best accuracy for the monitoring of storage & process tanks in both the industrial & marine sector. This all new gauge utilises the very latest in FMCW technology developed from the Military sector to offer non-invasive measurement of level at a competitive price.
The iRT is a cost effective level sensor designed for continuous non-contact level measurement
The primary head unit is mounted to a standard tank flange fitting. and can be removed under service conditions.
For long-distance transmission of level data, various standard communication interfaces (4 to 20mA, HART, MODBUS, PROFIBUS) are available for connection to plant control systems.
The primary head can also accept up to 4 additional 4-20mA input signals, for example from temperature and/or pressure transmitters. These are then retransmitted via the chosen digital output.
Communications
Various output standards are available to suit application requirements HART MODBUS PROFIBUS
Specification
System structure
Operating mode
Quartz-controlled dynamic PLL-stabilised FMCW radar in the X band (8.5 – 9.9 GHz) with digital signal processing; compact & modular design
Measured quantities
Primary quantity: distance; derived quantities: level, volume
Measuring range
Maximum measuring range: 30 m (100 ft)
Blocking distance
Minimum 0.2 to 0.5 m (0.65 to 1.6 ft),
Rate of change in level
£ 10 m/min (£ 33 ft/min)
Measured product conditions
Physical properties
Generally the product should have a relative permitivity of 3 or greater (er < 3) For er ³ 1.5 the product is still well recommended with application profiling.
Process temperature
Unrestricted but be aware of ambient and flange temperatures
Operating pressure
Cone antenna: -1 to +10 bar.
Component parts
Housing options
Epoxy coated cast aluminium. Optional— Stainless Steel DIN 1.4581 and ANSI 316 Ti.
Flange system and antenna
Stainless Steel 1.4435 (316 L) / PTFE
Gaskets
FFKM (Kalrez 4079); Kalrez 2035; Viton (FPM); PTFE is also in contact with the product in all versions
Process connection
Cone antenna
BS 4504-3.3:1989, BS1560-3.1:1989
ANSI B 16.5
DN 50 to DN 200, PN 6 to PN 64;
2” to 8”, 150/300 lb/RF
Rod antenna
Refer to separate data sheet
Electrical connections
Cable entries: M 25 x 1.5
Terminals: 0.5 – 2.5 mm2 (solid conductor: max. 4 mm2 )
Ambient conditions
Hazardous locations
BASEFA EEx d IIB T4, Zone 0, 1, 2 (EN50014, EN50018 Europe) - Pending
Type Approval
Lloyds Register - Pending
EMC
By design, EN 50081-1 Conducted and EN 50082-2 Radiated.
Protection category EN60529/IEC529
IP 67 to DIN 40050 / IEC 144
Shock resistance
Impact test to EN 61010, Sect. 8.2 with 0.5 J energy; drop test to prEN 50178
Vibration endurance limit
By design, IEC 68-2-6 and prEN 50178 (10-57Hz: 0.075mm / 57-150Hz: 1g) and possibly 1mm amplitude at 2-13.2 Hz / 0.7g acceleration at 13.2-100Hz
Salt spray test
3 week duration
Ambient temperature at signal transducer
Cone antenna: –20°C to +55°C (-24°F to +131°F)
Functional range: -40 °C to +170°C (-40°F to +158°F)
Flange temperature
Cone antenna (T ambient £ 50°C (122°F)): -20°C to +150°C (-22°F to +284°F)
Climate
Optional integral 10 watt electronics heater element.
Operator interface
Operator interface language
English
Units of measurement
Lengths: m, cm, mm, inch, ft, %,
Volume: m3 , Litre, US Gal, GB Gal, ft3, bbl, %
Conversion unit: any text
Power supply
24V ACDC
Standard: 18 – 31.2 V DC or 18 – 26.4 V AC (47-63 Hz)
Universal (115/230 V AC)
Optional: 100-240 V AC (tolerance: 85-264 V AC); 47-63 Hz
Power consumption
Typically 8.9W / 12.2VA
Current inputs
Additional inputs may be multiplexed meaning fewer cables are required on the vessel's deck.
Type
4 x Current input, active or passive
Current range
0(4)-20mA
Accuracy/linearity
0.5% (rel. 20 mA; 25°C/77°F)
Temperature drift
£ 300 ppm/K (typically 70 ppm/K)
Load
50 W (current), 10 kW (voltage)
Relay output Switching output (optional)
Nominal switching capacity (resistive load): 1 A 30 VDC, 0.3 A 125 VAC; On resistance £ 20 W; floating
Failure signal Current output
error signal: 2 mA (Exi = 3.6 mA)
Switching contact
contact opens or closes
Digital interfaces
error flags
Measuring accuracy Error of measurement
max. +/- 5mm (+/- 0.2”) or 0.1%
Repeatability
£ 0.5 x error of measurement
Measured-value resolution
1 mm (0.04”)